STAR DELTA STARTER
Starting
Electric Motors:
Due to their simplicity, robustness and
cost-effectiveness, squirrel-cage motors are the
preferred choice of industry. During start-up, they
develop currents of up to
approximately eight times the rated current and the high
starting torque linked to this.
The high starting currents often lead to unwelcome
voltage drops in the supply network
and the high starting torque put the mechanical elements
under considerable strain.
Therefore, the electricity companies determine limiting
values for the motor starting
currents in relation to the rated operational currents.
The permissible values vary from
network to network and depend on its load-bearing
capacity. With regard to mechanics,
methods are required which reduce starting torque.
Various starters and methods can be used to reduce
currents and torque:
• Star-Delta-Starting
• Auto-transformer-Starting
• Starting via chokes or resistors
• Multi-stage starting
• Starting using electronic soft starters
• Starting using frequency inverters
In the following passages, the main starting methods used
in practice are explained
further.
1
Traditional motor starting
1.1
Star-delta starting
A difference is made between:
• Normal Star-Delta Starters
• Enhanced Star-Delta Starters
• Star-Delta Starters with uninterrupted
switchover (closed transition)
1.1.1
Normal star-delta starters
To enable the motor to start, the motor
windings are configured in a star formation to the
supply voltage. The voltage applied to the
individual motor windings is therefore
reduced by a factor of 1√
_
3 = 0.58 this connection amounts to
approximately 30% of the
delta values. The starting current is reduced
to one third of the direct starting current, i.e.
typically to 2...2.5 Ie.
Due to the reduced starting torque, the
star-delta-connection is suitable for drives with a
high inertia mass but a resistance torque
which is low or only increases with increased
speed. It is preferably used for applications
where the drive is only put under a load after
run-up, i.e. for presses, centrifuges, pumps,
ventilators, etc.
Motor
Starting
After motor run-up, in most cases an
automatic timing relay controls the switch-over
from star to delta. The run-up using star
connection should last until the motor has
reached the approximate operational speed, so
that after switching to delta, as little postacceleration
as possible is required. Post-acceleration in
delta connection will instigate
high currents as seen with direct-on-line
starting. The duration of start in star connection
depends on the motor load. During delta
connection, the full mains voltage is applied to
the motor windings.
To enable a switch-over from star to delta,
the six ends of the motor winding are
connected onto terminals. The contactors of a
star-delta starter switch over the windings
accordingly.
Starting in star, the main contactor connects
the mains to winding endings U1, V1, W1.
The star contactor shorts winding endings U2,
V2, W2. After successful run-up, the star
contactor switches itself off and the delta
contactor connects terminals U1/V2, V1/W2,
W1/U2.
When changing from star to delta, attention
has to be paid to the correct phase sequence,
i.e. the correct connection of the conductors
to motor and starter. Incorrect phase
sequence can lead to very high current peaks
during the cold switch-over pause, due to
the easy torque reduction following re-start.
These peaks can damage the motor
windings and stress the controlgear
unnecessarily. The rotation of the motor has to be
considered as well.
Motor
Starting
A sufficient time period has to be maintained between the
star contactor’s deenergisation
and the energisation of the delta contactor, in order to
safely extinguish the
star contactor’s disconnecting arc before the delta
contactor is energised. During a
switch-over which is too fast, a short circuit may
develop via the disconnecting arc. The
switch over time period, however, should be just long
enough for an arc disconnection,
so that the speed decreases as little as possible.
Special timing relays for a star-delta
switch over fulfil these requirements.
Motor Protection and Contactor Sizing
The overload relay is situated in the motor line.
Therefore, the current to be adjusted is
lower than the motor’s rated current by a factor of 1√
_
3 = 0.58. Due to the third
harmonics currents circulating in the motor windings, a
higher setting of the overload
relay may be required. This may only be carried out on
the basis of utilising a
measuring device which records the correct r.m.s. value.
Conductor cross-sectional areas
must be of a suitable size in order that they will be
protected against temperature rises
resulting from overload conditions. Therefore, the conductor
size selected must be in
accordance with the protective device(s) rating.
For motor protection by means of power circuit breakers
with motor protection
characteristics, the power circuit breaker is switched
into the network supply lines, as it
also carries out short circuit protection of starter and
lines. In this case, the current is set
to the rated motor current. A correction of the set value
because of the third harmonics is
irrelevant under these circumstances. The lines are to be
thermally proportioned
depending on the power circuit breakers setting.
For normal star-delta starting, the controlgear must be
sized in accordance with the
following currents:
• Main contactor K1M 0.58 Ie
• Delta contactor K2M 0.58 Ie
• Star contactor K3M 0.34 Ie
For starting times exceeding approximately 15 seconds, a
bigger star contactor has to be
selected. If the star contactor is equal to the main
contactor, start times of up to
approximately one minute are permissible.
2. Soft starters:
2.1 General
Depending on the network supply quality, rapid load
current changes which occur
during motor start up can cause voltage drop which may
affect devices fed by the same
network:
• brightness fluctuations affecting lighting
• interference with computer systems
• contactor and relay drop outs
Mechanical machine or plant components are put under
severe stress by torque surges
which occur during starting.
Traditional solutions like
• Star-delta connection
• Autotransformer
• Chokes or resistors
can influence the voltage applied to the motor terminals
and, hence, the current, only
step by step.
The soft starter controls the voltage without steps from
a selectable starting value up to
100 per cent. This continuously increases the torque and
also the current. This means
that the soft starter enables loaded motors to be started
smoothly, without the steps
associated with electro-mechanical starters.
2.2 Soft
starter types
The differences between the different soft starter types
lie, above all, in the structure of
the power component and the control characteristics.
As already mentioned, the soft starter is based on the
phase angle principle. By means
of thyristors it is possible to switch at different
points the sine half wave and supply only
part of the mains voltage to the motor.
The thyristor permits the current to flow in one
direction only. This requires a second
semiconductor with opposite polarity which supplies the
negative current (back-to-back
switched semiconductors).
2.1 Single-phase full-wave
controlled soft starter
In case of the single-phase controlled soft starter, a
phase angle (Phase L2) is
implemented in a phase by means of two back-to-back
thyristors. The phases L1 and L3
are directly connected to the motor.
During start, approximately the 6 x rated motor current
still flows in phase L1 and L3. It
is only possible to reduce the current to the 3 x rated
current during the controlled
phase.
2.3 Three-phase half-wave controlled soft
starter
For a three-phase half-wave controlled soft starter, the
phase cut is implemented in all
three phases. A thyristor with an anti-parallel diode
serves as a power semiconductor.
This means that the phase control is only implemented in
one half-wave (half-wave
controlled). This means that the voltage is only reduced
during the half-wave when the
thyristor conducts. During the second half-wave, when the
diode conducts, the full
mains voltage is applied to the motor.
2.4.
Three-phase full-wave controlled soft starter
For this soft starter type, the phase control is
implemented in all three phases. Two backto-
back thyristors are used as power semiconductors. This
means that the phase voltage
is controlled in both half waves (full wave control). As
a result of the upper harmonics
occurring during phase control, the motor is nevertheless
put under a higher thermal
load than during a direct start.
0 comments:
Post a Comment